Flame Sensor
The flame scanners FFS07 and FFS08 are developed for the different, spectral bands of radiation as well as different types of fuel:
- Applicable for outdoor area usage
- FFS07 applicable Ex-Zone II
- FFS07 Ex applicable Ex-Zone I + Ex-Zone II
- Available types for UV and IR
- DIN EN 61508 Part 2 – SIL 3
Sensitivity gauging output: | > 10 m VAC (FFS07, FFS08 IR) |
|
Output parameter (Signal channel A+B) | Max. >70 Hz |
|
Protection Class: | IP66 / IP67 |
|
Environment temperature: | IR: -20 °C … +60 °C |
|
Relative humidity: | 0 % … 95 % not condensating |
|
Weight: | 0,4 kg |
|
Wear parts: | Non |
|
Approvals (in combination with F152):
|
EC type-examination certificate according to 2009/142/EC (Gas Appliance Directive)
SIL 3 Confirmation
CE Declaration of Confomity
Type examination Ex Zone 2 |
LAMTEC flame sensors are developed for different adiated spectrum and application/fuel.
Following application/fuel are possible:
- Oil
- Gas
- Biomass
- Chemical or other waste products
- Or a combination of those
Type | Spectrum / nm | Preferred application / fuels |
FFS07 UV-1 | 260 … 400 | Oil, gas |
FFS07 UV-4 | 215 … 360 | Oil, gas, special gases, such as refinery gas or blast furnace gas |
FFS07 IR-1 | 1,200 … 2,800 | Oil and gas combustion with strong flue gas re-circulation |