Compact Flame Scanner

F200K

  • Compact case with integrated flame sensor and switching amplifier
  • Intensity adjust in multiple steps
  • Digital circuit design for flame evaluation
  • Status indication by LEDs 24 VDC operating voltage
  • Two electronic channel system for fail safe operation and supervision
  • LED bar flame intensity indication and 4 (0) … 20 mA analog output
  • LED bar trend indication selectable for an optimum adjustment to the flame direction
  • Available with Class I, Division 2, Group A, B, C, D, Hazardous Locations
Tecnical Data
Power supply:24 VDC ± 20 %, ≤ 4,0 W 
Output contact:

≤ 42 VDC, ≥ 6 VAC/DC
≤ 0,5 A, ≥ 1,0 mA floating

Frequency range:10 … 190 Hz (F200K1 …)
10/20/30 … 190 Hz (F200K2 …)
Safety time ‘operation’:t ≤ 1 s (standard)
t ≤ 3 s (on request, at the factory)
Mode of operation:Continuous operation
Protection class:

IP66 / IP67
EX Zone I IP66
NEMA 4X

Operating temperature EX Zone II:

– 40°C…+75°C (UV-2, UV-3, IR-2) 

– 40°C… +60°C (IR-1) 

Operating temperature EX Zone I:

– 40°C…+ 65°C (UV-2, UV-3, IR-2)

– 40°C…+60°C (IR-1)

Dimension:Total length: 180 mm
Diameter: 40/80 mm
Weight:0,6 kg
Material:

Corrosion-resistant aluminium EN AW 6082 (seawater 2*; atmospheric condition 1*), nickel plated, varnished

* Comparative evaluation from 1 (very good) to 6 (unsuitable)

Approvals:

IECEx+Ex

     

    

 

EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298:2012-11

 

CE Declaration of Conformity

  • 2009/142/EC (Gas Appliance Directive)
  • 2014/68/EU (Pressure Equipment Directive)
     

ANSI / UL 1998, 2nd Edition in Combination with ANSI / UL 372, 5th Edition and UL353, 5th Edition

Available with Class I, Division 2, Group A, B, C, D, Hazardous Locations

Purpose

In single-burner and multiple-burner furnaces, the flame detector performs a high-safety monitoring of the burner flames. When the flame switches off, the safe control state “Flame off” is reached.

The flame detector is mainly used in large-scale power plants, thermal power stations and chemical plants as well as for monitoring furnaces which are operated with:

  • Oil
  • Gas
  • Bio-mass
  • Dust coal
  • Chemicals and other waste products
Selection Criteria
TypeSpectrum / nmPreferred application / fuels
F200K1 UV-2
F200K2 UV-2
210 … 380Oil, gas (special gases of refinary- or blast furnaces)
F200K1 UV-3
F200K2 UV-3
F200K1 IR-2
F200K2 IR-2
850 … 1200Oil, gas, coal, firing with high flue gas recirculation,
waste gases with yellow colour without UV-radiation
respectively with absorbtion of the UV-radiation by
vapor or dust etc.
F200K2 IR-1
F200K2 IR-1
1200 … 2800Coal dust

F200K Ex

  • Compact case with integrated flame sensor and dual amplifier for fail safe operation
  • Intensity adjust in multiple steps
  • Digital circuit design for flame evaluation
  • Status indication by LEDs
  • 24 VDC operating voltage
  • Two electronic channel system for fail safe operation and supervision
  • LED bar flame intensity indication and 4 (0) … 20 mA analog output
  • SIL 3 following DIN EN 61508-2
Tecnical Data
Power supply:24 VDC ± 20 %, ≤ 4,0 W 
Output contact:

≤ 42 VDC, ≥ 6 VAC/DC
≤ 0,5 A, ≥ 1,0 mA floating

Frequency range:10/20/30 … 190 Hz
Safety time “operation”:t ≤ 1 s (standard)
t ≤ 3 s (on request, at the factory)
Mode of operation:Continuous operation
Protection class:IP66 / IP67
NEMA 4X
Operating temperature:-20 °C … +60 °C 
Dimension:Total length: 216 mm
Diameter: 60/90 mm
Weight:2 kg
Material:

Corrosion-resistant aluminium EN AW 6082 (seawater 2*; atmospheric condition 1*), anodised

* Comparative evaluation from 1 (very good) to 6 (unsuitable)

Approvals:

IECEx+Ex

GL

EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298:2012-11

 

SIL 3 Confirmation

  • DIN EN 61508 Part 2

 

CE Declaration of Conformity

  • 2009/142/EC (Gas Appliance Directive)
  • 2014/68/EU (Pressure Equipment Directive)
 
Purpose

After establishing the compact flame monitor F200K successfully and it is proven that it is at its best with combustion of any kind (oil, gas etc.), LAMTEC now offers this compact flame monitor in explosive proof design for different issues.
The following type shows a wide range of applications for combustion plants especially for the chemical or petrochemical industry.

Sensitivity features:

  • 2 sensitivity sections
  • 6 steps selectable for each sensitivity section
  • externally switchable
  • Increased sensitivity in section 2
Selection Criteria
TypeSpectrum / nm          Preferred application / fuels
F200K1 UV-2 Ex
F200K1 UV-2 Ex II
F200K2 UV-2 Ex
F200K2 UV-2 Ex II
210 … 380 Oil, gas (special gases of refinary- or blast furnaces)
F200K1 UV-3 Ex
F200K1 UV-3 Ex II
F200K2 UV-3 Ex
F200K2 UV-3 Ex II
210 … 380 Oil, gas (special gases of refinary- or blast furnaces)
F200K1 IR-1 Ex
F200K1 IR-1 Ex II
F200K2 IR-1 Ex
F200K2 IR-1 Ex II
1200 … 2800 Oil, gas, coal, firing with high flue gas recirculation,
waste gaseswith yellow colour without UV-radiation
respectively with absorbtion
of the UV-radiation by vapor or dust etc.

F300K

  • 3 operating modes
  • 14 frequency ranges
  • Available as single or double sensor (IR/UV)
  • Degree of protection IP67
  • Flame ON/OFF self-learning function
  • Operation via graphic User Interface with status display (optional)
  • SIL 3 according to DIN EN 61508 part 1-7
  • Available with Class I, Division 2, Group A, B, C, D, Hazardous Locations
Tecnical Data
Supply voltage:24 VDC ± 20 % ≤ 3,5 W
Flame and fault contact:≤ 50 VDC, ≥ 6 VDC
≤ 0,5 A, ≥ 1,0 mA floating
Frequency range:10 / … / 110 … 210 Hz
7 levels in the standard version
Safety time “Operation”:t ≤ 1 sec. (standard)
t ≤ 1, 2, 3, 4, 5 sec. (selectable via password)
Operating mode:Continuous operation
Degree of protection:IP66 / IP67
NEMA 4X
Operation temperature:-40 °C … + 85 °C
Dimensions (HxT):99×195,5 mm
Weight:1,05 kg (aluminium)
3,6 kg (stainless steel)
Material:

Corrosion-resistant aluminium EN AW 6082 (seawater 2*; atmospheric condition 1*), anodised
or stainless steel

* Comparative evaluation from 1 (very good) to 6 (unsuitable)

Approvals:

CE

TUEV

DVGW

CSM

FMA

AGA


EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298:2012-11

 

SIL 3 Confirmation

  • DIN EN 61508 part 1-7

 

CE Declaration of Conformity

  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
  • 2014/68/EU (Pressure Equipment Directive Cat. 4 module B+D)
  • 2009/142/EC (Gas Appliance Directive)

 

ANSI / UL 1998, 2nd Edition in Combination with ANSI / UL 372, 5th Edition and UL353, 5th Edition

Type examination certificate Ex Zone 2

Available with Class I, Division 2, Group A, B, C, D, Hazardous Locations

 

Purpose

The compact flame monitor is a safety device and complies with the following standards among others:

  • DIN EN 298 for gas operation
  • DIN EN 230 for oil operation
  • IEC 6158, SIL 3


Directives:

  • 2014/68/EU (Pressure Equipment Directive)
  • 2009/142/EC (European Gas Appliances Directive)
  • Field of application:
    Combustion plants with and without selection tasks
    Single and combi-burners
    Power plants, heating plants, process combustion,


Fuels:

  • Oil
  • Gas
  • Dust
  • Biomass
  • Coal
  • Process gases
Selection Criteria
TypeSpectrum / nmPreferred applications / fuels

F300K UV-4


215 … 360
 
  • Oil
  • Gas
  • Special gases such as refinery gases,
    blast furnace gases and hydrogen
 
F300K IR-2850 … 1200 
  • combustion chamber monitoring
 
F300K IR-31000 … 1700 
  • Oil, gas, wood, coal and dust-fired furnaces
    with a high level of flue-gas recirculation
  • Yellowish waste gases without UV radiation
    or with shielding of the UV spectrum by
    water vapour and dust
 
F300K IR-41000 … 2200
F300K UVIR-1215 … 360
850 … 1700
UV:Oil, gas, special gases like refinery gases and furnace gases
IR: Oil, gas, wood, coal, dust furnaces with strong flue-gas recirculation,
waste gases with yellowish colour without UV radiation or with shielding