Burner Tronic BC300

  • Burner control unit for thermal process plants
  • Suitable for burners in cyclic operation, 2-stage operation and pneumatic modulating 
  • Adjustable via PC
  • Easy-to-read icon to show burner status
  • Connection to PLC is possible
Technical Data
Power supply:230 V +10/-15 % 47-63 Hz
120 V +10/-15 % 47-63 Hz (on request)
Maximum pre-fuse:10 A slow-blow
Power consumption:Max. 30 VA
Digital inputs:

Max. cable length 10 m / 32.8 ft
Max. cable length 20 m / 65.6 ft for the following signals:
Burner stage 1 / Burner stage 2
Safety interlock chain system
Purge
Reset
Alarm

Digital Outputs:

2 fuel valves max. 1 A cos φ 0.4
Relay for single electrode operation max. 1 A cos φ 0.4
Combustion air valve max. 2 A cos φ 0.4
Operating mode indication max. 2 A cos φ 0.4
Spark igniter max. 2 A cos φ 0.2
Alarm output max. 1 A cos φ 0.3

Number of programming operations:Unlimited (EEPROM)
Fieldbus coupling (optional):PROFINET
Housing:Polycarbonate + ABS
Dimensions (H x W x D):200 x 1 15 x 61 mm / 7.87″ x 4.53″ x 2.40″ in
Weight:1.0 kg / 2.2 lb

Approvals:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EC Type Examination Certificate according to 2016/426 A III B (Gas Appliance Directive)

  • DIN EN 298:2012-11
  • DIN EN 13611:2011-12
  • DIN EN 60730-2-5: 2015-10

 

SIL 3 Confirmation

  • DIN EN 298:2012-11
  • DIN EN 61508:2011 (parts 1-7)
  • DIN EN 13611:2011-12
  • DIN EN 13611:2016-09
  • DIN EN 50156-1:2016-03 clause 10.5
  • DIN EN 50156-2:2016-03

 

CE Declaration of Conformity

  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
  • (EU) 2016/426 (Gas Appliance Regulation GAR)
  • 2011/65/EU (RoHS)
 

 

Purpose

The BC300 is a burner sequencer for industrial burners on thermal process plants. It is designed for use on burners of all sizes in intermittent and continuous operation. The control output can be single stage or two stage, with pneumatic modulation or in cycle operation. The flame can be monitored either with ionisation in single electrode or twin electrode operation, UV tube or F152 with FFS07 or FFS08 optical sensors. The BC300 is also suitable for applications with process temperatures higher than 750 °C. The UI300 user interface can be used to monitor the status of the burner at distance and in low light levels. Intuitive graphics and symbols are used to make the UI300 language neutral and easy to understand. Changes to the settings can be modified on-site with the LSB Remote Software. For error diagnostics, the last 10 faults are saved to the device. A comprehensive list of approvals ensures that the BC300 is suitable for worldwide use.