ETAMATIC OEM

  • Burner control system
  • Electronic compound, up to 4 channels
  • Connects to PLC systems
  • Simple to program
  • 10-bits resolution
  • Can be operated from PC
  • Integrated load control
  • Integrated leakage test
  • CO/Ocontrol integrated
  • Can be installes directly on the burner
Tecnical Data
Power supply:From 115 VAC -15 %
To 230 VAC +10 % 50/60 Hz
Ambient temperature
operation:

+0 °C … +60 °C
Ambient temperature
Transport and storage:

-25 °C … +60 °C
Resolution, per
analogue input:

999 digit, 10 bit

Recommended running-time for actuators:

30 s … 60 s
Continuous outputs:0…10 V > 5 kΩ
Load:0/4 … 20 mA < 600 Ω
Digital signal input:

14 (The line shall not be longer than 10 m)

Digital outputs:Main gas 1, main gas 2, oil valves, ignition valves, ignition transformer, fan, oil pump, fault
Number of curve sets:2 per channel (e.g. for oil/gas multi-burner)
BUS connection:

Via  LSB-adapter BUS-connection optional for:
     • Interbus-S (Phoenix)
     • PROFIBUS DP
     • Modbus
     • Ethernet (Modbus TCP)

Approvals:

EC Type Examination Certificate

SIL 3 Confirmation

TUEV

DVGW

AGA

GL

EAC

 

 

EC Type Examination Certificate according to 2014/68/EU
(Pressure Equipment Directive)

  • DIN EN 298
  • DIN EN 1643
  • DIN EN 230
  • DIN EN 60730-2-5
  • DIN EN 12067-2
  • DIN EN 50156-1
     

EC Type Examination Certificat according to 2009/142/EC
(Gas Appliance Directive)

  • DIN EN 298
  • DIN EN 13611
  • DIN EN 1643
  • DIN EN 12067-2
     

SIL 3 Confirmation

  • DIN EN 61508 Part 2+3
     

CE Declaration of Confomity

  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
  • 2014/68/EU (Pressure Equipment Directive Cat. 4 Mod. B+D)
  • 2009/142/EC (Gas Appliance Directive)
 

System Acceptance Test- EN 50156-1 (TÜV)
 

Marine Type Approval GL and LR
 

AGA Certified Product – EN298, AS4625, AS4630
Purpose

The ETAMATIC OEM is specially designed for installation in the burner. Additional costs are saved through short wiring paths. The ETAMATIC OEM is therefore particularly suitable as standard equipment for monoblock burners.

The Startup Manager for ETAMATIC OEM supports the commissioning engineer during the initial installation of the burner as well as during adjustments of the burner settings by means of assistants.

Selection Criteria
Function  Communication  Optional

 

  Start-up counter

 

 


  RS232 interface:
     • Operating
     • Maintaining
     • Remote control
     • Storage
 


  CO/O2 control

 

 

  Operating hours counter

 

 

  LAMTEC System Bus (LSB)  

 


  Flame monitoring

 

 

  Burner control unit

 

 


  Control instrumentation connection – options:
     • INTERBUS-S
     • Profibus
     • Modbus
 


  Frequency converter

 

 

  Compound regulator
     • 4 positioning elements

 

 


  Start-up assistant

 

 

  Burner firing-rate controller 

 

 


  Plug kits
     • Inverse terminal
     • Terminal with
         elasticity

 

 

  Leakage test